← Search CVEs

CVE-2026-102076

HIGH 8.7

Published 2026-10-13 · Last modified 2026-10-13

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate user-supplied input in upload code. This could allow an unauthenticated remote attacker to cause a denial of service.

ELEVATED IMPACT

Severe if exploited (CVSS 8.7), but no known exploitation and low modeled probability. Patch on a normal cadence.

Exploitation likelihood

0.4%chance of exploitation in 30 days · 36th percentile

○ In CISA KEV ○ Catalogued PoC

Impact if exploited

8.7CVSS 4.0 · HIGH

  • ConfidentialityNone
  • IntegrityNone
  • AvailabilityHigh

What an attacker needs

  • ✓Access: Reachable over the network — no local access needed
  • ✓Privileges: No account or privileges required
  • ✓User interaction: No user interaction needed
  • ✓Complexity: No special conditions — reliably repeatable
  • ✓Requirements: No special attack requirements

✓ lowers the bar for an attacker · ⚠ raises it

Proof of concept

No public PoC is currently catalogued.

Search for new PoCs

Search GitHub now — results may be empty or unverified.

Tracked sources are checked daily for recent CVEs, including PoCs published after the original disclosure. A later release appears after a tracked source lists it and a refresh succeeds.

Data snapshot:

Affected

Vendors Siemens

Products Apogee Mbc (Ppc) (Bacnet) Apogee Mbc (Ppc) (P2 Ethernet) Apogee Mec (Ppc) (Bacnet) Apogee Mec (Ppc) (P2 Ethernet) Apogee Pxc Compact (Bacnet) Apogee Pxc Compact (P2 Ethernet) Apogee Pxc Modular (Bacnet) Apogee Pxc Modular (P2 Ethernet) Talon Tc Compact (Bacnet) Talon Tc Modular (Bacnet)

Weakness (CWE)

  • CWE-121: : Stack-based Buffer Overflow

CVSS vector

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

References and research data (JSON)

All CVSS metrics

  • HIGH 7.5 v3.1 · CNA Primary
    CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
  • HIGH 8.7 v4.0 · CNA Primary
    CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
  • HIGH 8.7 v4.0 · NVD Secondary
    CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
  • HIGH 7.5 v3.1 · NVD Secondary
    CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

References

Technical & other

Sources: NVD · CVE.org · EPSS